Notes on installation of power cables

1cable and heat pipe parallel installation, should keep 2m distance, cross should maintain 0.5m.
2
the cable and other pipes in parallel or cross installation, to maintain the distance of 0.5m.
3
when the cable is installed directly, the buried depth of 1-35kV cable shall be no less than 0.7m.
4
10kV and below cable parallel installation, mutual net distance is not less than 0.1M, 10-35kV is not less than 0.25m, cross distance is not less than 0.5m.
5
the minimum bending radius of cable, multi-core cable shall not be less than 15D, single core cable shall not be less than 20D (D for cable diameter).
6
6kV and above cable joint
  a
、installation of cable terminal, must be stripped of semi conductive shielding layer, the operation may damage insulation, should avoid marks and uneven situation, when necessary using sandpaper; shielding ends should be formed, and the graphite layer (carbon particles) clean.
  b
、plastic insulated cable end copper shield and the steel armor must be well grounded, the short line should also follow this principle, to avoid unbalanced operation when the steel armor end dynamic induction, even sparking and burning accident of sheath. Ground outlet to the tin copper and iron soldering copper cable application connection, should not be used to avoid burning torch welding, insulation.
  c
three-phase copper shielding should be respectively connected with a ground line, pay attention to shield grounding wire and steel armor wire should be insulated from each other are led, welding wire position should be under.
7
the basic requirements for the cable terminal head and middle connector: A. B. good conductors; reliable insulation, recommended the use of irradiation cross-linked heat shrinkable silicone rubber insulation material; C. good seal; D. enough mechanical strength, can adapt to various operating conditions.
8
cable ends must be waterproof, corrosion and other corrosive materials, to prevent the insulation aging and breakdown caused by water tree.
9
cable loading and unloading must use the crane and forklift, prohibit flat, flat, large cable installation must use cable car, so as to avoid cable by external force damage or artificial drag and scrape the sheath and insulation layer. The cable is not mounted, so the conductor is not allowed to be bent by hand. The conductor is damaged and the insulation is short circuited.
10
if the cable can not be laid in time, it should be stored in a dry place, to prevent sunlight exposure, cable end water inlet and so on.
Attention: the installation of wires and cables should be done by the installation personnel or full-time technical personnel who are familiar with the performance of wires and cables. If there are still unclear matters, please consult the relevant technical department or our technical department in a timely manner.

0.6/1KV copper core PVC insulated power cables are installed in air for long term continuous load, allowing ampacity


Section
mm2

Allowable Ampacity for long term continuous load(A

No armour

Armored

Single core

Double core


Three core

Five core

Single core

Double core

Three core

Five core


2
root

3root

Four core


4+1)core



2
root


3root

Four core


4+1)core





3+1)core

3+2)core





3+1)core

3+2)core

1.5
2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

28
36
47
60
83
109
138
173
207
264
322
374
431
495
587
673
794
920
1058

23
30
39
49
68
89
113
142
170
216
264
307
353
406
491
552
652
754
868

26
33
44
16
77
101
128
161
193
246
299
348
401
460
546
626
738
856
984

20
26
37
44
61
82
104
127
155
190
242
282
322
368
--
--
--
--
--

--
--
30
37
53
69
89
109
132
167
213
242
282
322
385
431
--
--
--
--

--
--
31
38
54
70
91
111
135
170
217
247
288
328
393
440
--
--
--

28
36
47
60
83
109
138
173
207
264
322
374
431
495
587
673
794
920
1058

23
30
39
49
68
89
113
142
170
216
264
307
353
406
481
552
652
754
868

26
33
44
56
77
101
128
161
193
246
299
348
401
460
546
626
738
856
984

--
--
38
45
62
84
106
130
158
194
247
288
328
375
--
--
--
--
--

--
--
31
38
54
70
91
111
135
170
217
246
287
327
392
439
--
--
--

--
--
32
39
55
71
91
112
137
173
221
250
290
330
398
445
--
--
--

0.6/1KVPermissible load carrying capacity of aluminum core PVC insulated power cables under long continuous load in air


Nominal cross section(mm2

Allowable Ampacity for long term continuous load(A

No armour

Armored

Single core

Double core


Three core

Five core

Single core

Double core

Three core

Five core

2root

3root

Four core

4+1)core


2
root

3root

Four core

4+1)core





3+1)core

3+2)core





3+1)core

3+2)core

2.5
4
6
10
16
25
35
50
70
95
120
150
185
240
300
400
500
630

28
37
48
63
84
110
132
161
201
247
288
334
385
454
523
621
725
851

23
30
40
52
69
90
108
132
165
203
236
274
316
372
429
509
595
695

26
34
45
59
78
102
123
150
187
230
268
311
358
422
486
578
674
791

21
28
37
48
63
81
99
121
150
190
219
247
288
--
--
--
--
--

17
23
30
40
54
69
85
104
132
161
190
219
247
299
339
--
--
--

17
23
31
41
55
70
87
106
135
164
194
223
282
305
346
--
--
--

28
37
48
63
84
110
132
161
201
247
288
334
385
454
523
621
725
851

23
30
40
52
69
90
108
132
165
203
236
274
316
372
429
509
595
698

26
34
45
59
78
102
123
150
187
230
268
311
358
422
486
578
674
791

--
28
37
48
63
81
99
121
150
190
219
247
288
--
--
--
--
--

--
23
30
40
54
69
85
104
132
161
190
219
247
299
399
--
--
--

--
23
31
41
55
70
87
106
135
164
194
223
252
305
346
--
--
--

0.6/1kVPermissible load carrying capacity of XLPE insulated power cables under long continuous load in air


0.6/1kVXLPE insulated power cable

Rated voltageU/U

0.6IkV

Model

YJVYJLVYJYYJLY

YJVYJLVYJYYJLYYJV22YJLV22YJY23YJLY23YJV32YJLV32YJY33YJLY33

Core number

Single core

Double core

3-5core

Laying

In the air

In soil

In the air

In soil

In the air

In soil

Single core cable arrangement



Conductor material

Cu

AI

Cu

AI

Cu

AI

Cu

AI

Cu

Al

Cu

Al

Cu

AI

Cu

AI

Nominal cross section(mm2


1.5
2.5

22
30

---
---

30
40

---
---

40
50

---
---

43
57

---
---

2533

---
---

36
47

---
---

21
28

---
---

25
33

---
---

4
6

39
50

---
---

53
67

---
---

71
91

---
---

74
94

---
---

44
55

---
---

63
78

---
---

37
46

---
---

44
54

---
---

10
16

70
94

53
76

93
124

71
102

123
158

95
122

127
163

97
131

77
101

48
82

105
135

80
112

63
84

48
65

73
94

56
72

25
35

124
154

99
118

168
207

130
160

201
244

159
191

213
258

165
199

140
173

106
130

189
217

139
169

109
132

85
102

120
144

93
111


50
70


191
241


150
185


252
306


195
239


292
355


224
283


304
372


235
289


218
264


150
191


258
315


198
246


159
195


123
152


159
205


131
159

95
120

297
346

231
268

384
439

298
340

433
496

338
387

449
512

348
398

331
379

256
293

377
422

293
334

237
273

184
213

240
278

190
210

150
185

399
455

308
365

507
591

392
459

554
624

430
490

575
650

445
505

439
498

336
388

482
540

372
422

310
355

241
277

309
347

240
271

240
300

552
652

427
502

694
810

539
629

725
819

568
639

757
855

589
664

---
---

---
---

---
---

---
---

416
473

326
372

399
446

312
351

400
500

777
921

590
687

937
1078

731
845

934
1061

701
898

976
1110

762
870

---
---

---
---

---
---

---
---

---
---

---
---

---
---

---
---

Ambient temperature(

40

25

40

25

40

25


6/66/10kV XLPE insulated power cable

Rated voltage U/U

66610kV

Model

YJVYJLVYJYYJLY

YJVYJLVYJYYJLYYJV22YJLV22YJY23YJLY23YJV32YJLV32YJY33YJLY33

Core number

Single core

Three core

Laying

In the air

In soil

In the air

In soil

Single core cable arrangement





OOO






OOO

Conductor material

Cu

Al

Cu

Al

Cu

A1

Cu

A1

Cu

A1

Cu

Al


Nominal cross section (mm2

25
35

140
170

110
135

165
205

130
155

150
180

115
135

160
190

120
145

120
140

90
110

125
155

100
120

50
70

205
260

160
200

245
305

190
235

215
265

160
200

225
275

175
215

165
210

130
165

180
220

140
170

95
120

315
360

247
280

370
430

290
335

315
360

240
270

330
375

255
290

255
290

200
225

265
300

210
235

150
185

410
470

328
365

490
560

380
435

405
455

305
345

425
480

330
370

330
375

255
295

340
380

260
300

240
300

555
640

435
500

665
765

515
595

530
595

400
455

555
630

435
490

435
495

345
390

435
485

345
390

400
500

745
815

585
680

890
1030

695
810

680
765

520
595

725
825

565
650

565
---

450
---

520
---

440
---

Ambient temperature(

40

25

40

25

8.7/108.7/15KV XLPE insulated power cables are laid in air for long term continuous load, allowing ampacity


8.7/108.7/15KV XLPE insulated power cable

Rated voltage
U/U

8.7108.715tv

Model

YJVYJLVYJYYJLY

YJVYJLVYJYYJLYYJV22YJLV22YJY23YJLY23YJV32YJLV32YJY33YJLY33

Core number

Single core

Three core

Laying

In the air

In soil

In the air

In soil

Single core cable arrangement





000





000

Conductor material

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Cu

A1


Nominal cross section(mm2

25
35

140
170

110
135

165
205

130
155

150
180

115
135

160
190

120
141

120
140

90
110

125
115

100
120

50
70

205
260

160
200

245
305

190
235

215
265

160
200

225
275

175
215

165
210

130
165

180
220

140
170

95
120

315
360

247
280

370
430

290
335

315
360

240
270

330
375

255
290

255
290

200
225

265
300

210
235

150
185

410
470

328
365

490
560

380
435

405
455

301
345

425
480

330
370

330
375

255
295

340
380

260
300

240
300

555
640

435
500

665
765

515
595

530
595

400
455

555
630

435
490

435
495

345
390

435
485

345
390

400
500

745
855

585
680

890
1030

695
810

680
765

520
595

725
825

565
650

565
---

450
---

520
---

440
---

Ambient temperature(

40

25

40

25

26/35KV XLPE insulated power cables are laid in air for long term continuous load, allowing ampacity


26/35KV XLPE insulated power cable

Rated voltage
U/U

2635kV

Model

YJVYJLVYJYYJLY

YJVYJLVYJYYJLYYJV22YJLV22YJY23YJLY23YJV32YJLV32YJY33YJLY33

Core number

Single core

Three core

Laying

In the air

In soil

In the air

In soil

Single core cable arrangement





ooo





ooo

Conductor material

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Cu

Al

Nominal cross section (mm2

50
70

220
270

170
210

245
305

190
235

215
265

165
200

225
275

175
215

185
230

145
190

200
250

170
190

95
120

330
375

255
290

370
425

285
330

315
360

240
270

330
375

255
290

280
310

215
240

300
330

230
255


150
185


425
485


330
380


485
555


375
430


400
455


305
345


420
475


325
370


360
400


280
310


380
425


295
330

240
300

560
650

435
510

650
745

505
580

525
595

400
455

555
630

430
490

470
540

365
430

490
555

380
435

400
500

760
875

595
690

870
1020

680
790

680
775

525
600

720
825

565
645

610

---

485
---

625
---

500
---

630

1000

800

1160

920

875

685

940

740

---

---

---

---

Ambient temperature(

40

25

40

25

Current rated voltage 0.6/1kV PVC insulated power cables are laid in air for long term continuous load, allowing current carrying capacity


Rated voltage 0.6/1kV PVC insulated power cable

7.1.1 cable laying temperature more than 0 DEG C
Allowed working temperature of cable conductor: 7.1.2 is not higher than 70 DEG

7.1.3  7.1.3 short-circuit (the longest duration is more than 5S) the maximum working temperature of the cable: 160 degrees centigrade
7.1.4 cable allows minimum bending radius R=15D. (D is the actual external diameter of the cable)
7.1.5 cable shall be subjected to DC voltage 3500V/5min without breakdown.
7.1.6 laying in air

       A. single core cable parallel laying of the center distance: 185mm2 and below for the cable diameter of 2 times; 240mm2 and above is 90mm.
B. ambient temperature: 30 C.
C. correction factor for download flow at different ambient temperatures:

Ambient temperature()In the air

20

25

30

35

40

45

Correction factor

1.12

1.06

1.00

0.94

0.87

0.79

Correction factor 7.1.7 directly buried laying
When the A. single core cable is not in contact with the cable, the center distance is 2 times of the cable diameter.
B. ambient temperature: 25 C.
C. soil thermal resistance coefficient: 10.M/W
D. buried depth: 0.7m
E. correction factor of download flow at different environmental temperatures:

Ambient temperature()In soil

15

20

25

30

35

Correction factor

1.11

1.05

1.00

0.94

0.88

Rated voltage 26/35 (26/45) kV and below. XLPE insulated power cables are laid in air, allowing current carrying capacity under long-term continuous load


XLPE insulated power cables rated voltage 26/35 (26/45) kV and below

1 cable laying temperature more than 0 DEG C
Allowed working temperature of cable conductor 2: less than 90 DEG C
3 short circuit (the longest duration is more than 5S) the maximum working temperature of the cable: 250 degrees centigrade
4 cable allows minimum bending radius R=15D. (D is the actual external diameter of the cable)
5 lay in the air
A. single core cable parallel laying of the center distance: 185mm2 and below for the cable diameter of 2 times; 240mm2 and above is 90mm.
B. ambient temperature: 40 C.
C. correction factor for download flow at different ambient temperatures:
Direct buried laying
When the A. single core cable is not in contact with the cable, the center distance is 2 times of the cable diameter.
B. ambient temperature: 25 C.
C. soil thermal resistance coefficient: 10.M/W
D. buried depth: 0.7m
E. correction factor of download flow at different environmental temperatures:

The operating temperature of the conductor is90

Soil temperature(

10

15

20

25

30

35

40

45

Correction factor

1.11

1.07

1.04

1.00

0.96

0.92

0.87

0.83

The operating temperature of the conductor is90

Air temperature(

10

15

20

25

30

35

40

45

50

Correction factor

1.26

1.22

1.18

1.14

1.09

1.04

1.0

0.94

0.89